We heat, cool and improve energy efficiency by   offering heat pumps, chillers and clean energy technology
You are here: Withair® » Products & Solutions » Hot Water & Direct fired Single/Double effect Absorption Chiller

loading

Share to:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
sharethis sharing button

Hot Water & Direct fired Single/Double effect Absorption Chiller

  • W02C3 Series

  • WithAir®

  • 8418692090

Product Description

WithAir® Hot Water Absorption Chiller ,adopts  hot water to make cool (including to use hot water from solar).

 WithAir® Integrated Hot Water Type Central Air Conditioning


Features and Benefits

—— Product Features ——
 
 Cooling capacity: from 18Ton and above.
 

 Fuel: Natural gas or diesel oil or bios.

 Refrigerator: Water.

 Absorber: Lithium bromide solution.
 
 Inhibitor: Lithium chromate or Lithium molybdate.
 
 Working pressure: 0.1 or 0.4 or 0.6 or 0.8MPa.
 


Technical Parameters

Model   W02C3-
18GH 30GH 58GH 86GH 114GH 175GH
Cooling capacity Hot water + Fuel kW 63.3 105.5 204.0 302.5 400.9 615.5
Ton 18 30 58 86 114 175
10³kcal 54.4 90.7 175.4 260.1 344.7 529.2
Btu/h 216,000 360,000 696,000 1,032,000 1,368,000 2,100,001
Hot water only kW 38.7 63.3 123.1 186.4 242.7 369.3
Ton 11 18 35 53 69 105
10³kcal 33.3 54.4 105.8 160.3 208.7 317.5
Btu/h 132,000 216,000 420,000 636,000 828,000 1,260,000
Heating capacity kW 56.3 95.0 186.4 281.4 372.8 569.8
Ton 16 27 53 80 106 162
10³kcal 48.4 81.7 160.3 241.9 320.6 489.9
Btu/h 192,000 324,000 636,000 960,000 1,272,000 1,944,001
A/C water Cooling °C 12/7 (11/8 hot water use only)
Heating °C 55.4/60
Flow rate m³/h 10.0 16.4 32.8 49.1 76.0 100.0
Pressure drop kPa 80
Pipe diameter DN 40 50 65 80 100 125
Hot water Flow rate m³/h 8.6 14.3 28.5 42.8 57.0 86.0
Inlet/outlet Temperature °C 90/85
Pipe diameter DN 40 50 65 80 100 125
Pressure drop kPa 80 80 90 90 90 100
Cooling water Flow rate m³/h 18.0 30.0 60.0 90.0 120.0 180.0
Inlet/outlet Temperature °C 32/35
Pipe diameter DN 40 50 65 100 125 125
Pressure drop kPa 80 80 80 90 90 100
Consumption Natural gas(cooling/heating) Nm³/h 5.8/6.1 9.5/9.9 19.0/19.8 28.5/29.7 38.0/39.6 58.0/60.0
Electricity kW 0.75 0.9 1.7 2.1 2.5 3.8
Dimension Length mm 1,700 1,900 2,820 2,550 3,300 4,000
Width mm 1,450 1,600 1,950 2,300 2,400 2,500
Height mm 1,800 2,000 2,200 2,450 2,450 2,450
Weight Net weight kg 1,600 2,500 3,300 4,800 6,500 8,600
Gross weight kg 1,800 2,700 3,600 5,100 6,800 9,100
The data in the above table test as following:
1. The burning calorific value of town gas is 10kmh/m³;
2. Optional parts:cooling water tower, chilled water pump, cooling water pump, hot water adjusting valve, filter of chilled & cooling water, vacuum pump;
3. Fouling factor for chilled water,cooling water and hot water :0.086m²·h·°C/kW(0.0001m²·h·°C/kcal);
4. The standard gague pressure limit for chilled water,cooling water and hot water lower than 0.8Mpa;
5. The data in this table are for reference only, please following the nameplate parameter of this product.

Packaging & Transportation

-
Wi thAir ® pr ovide s two styles package for different transporation modes:
(1). St andard package(free of charge): heat pump is wrapped with plastic film, which is suitable for container shipment & a few transshipment cargo;
       withair heat pump package_3withair heat pump shipment
(2). Special pac kage(extra charge): heat pump is wrapped with plastic film and wooded box, which is suitable for bulk cargo transporation; 
       withair heat pump package_1

Optional Installation Accessories

     In order to service heat pumps system installation for clients,WithAir® also provide pressional Parts & Supplies and Technical Information for your engineering support,research and repair, such as: Thermostat Controls, Cooling Towers,Heat Exchangers, Insulation Materials, Water Tank, Expansion Tank, Water Pumps, Water Valves, Flow Gague, Pressure Gauge, Air Duct, Filters, Hydraulic Module (kits) and so on.

     Please take a look at Parts & Supplies lines for more information.
Previous: 
Next: 
Get Best Quote

Quick Links

Product Category

Get In Touch

   Withair Group (China) Limited
   Withair (Nanjing) Industries Co., Ltd
    Office number: + 86 25 86696286
    Mobile number: + 86 13915928183 (WhatsApp)
    E-mail address: info@withair.cn ; jed@withair.cn
    Factory A: No.6 Lukou Chuangzhi Industrial Park, Nanjing,China,211113
    Factory B: No.9 Dongshan Bridge Industrial Park, Nanjing,China,211153
Home
 Withair® 2007 ~ 2021 All Rights Reserved