Modular Air Cooled Heat Pump

  • W01R1 Series

  • Withair® / OEM brand as option

  • 8418612090

  • 72.0 ÷ 565.0 kW / 20.0 ÷ 160.0 Tons

  • 76.0 ÷ 592.0 kW / 21.6 ÷ 174 Tons

  • 3.35 EER / 3.66 COP

  • Compressor - 5 year limited ; Other parts - 2 year limited

  • R410A, R407C,R22 as option

  • Scroll type; HITACHI, Daikin, Panasonic, MITSUBISHI,Copeland

  • High efficiency shell-and-tube heat exchanger

  • High efficiency Hydrophilic aluminum finned copper pipe heat exchanger

  • Commercial Use, Industrial Use

  • 380V/3Ph/50Hz (400V/415V/3Ph/50Hz, 230V/380V/460V/3Ph/60Hz as option)

  • Withair® Big Size Modular Air Cooled Water Chillers & Heat Pumps Catalogue (2021 Version).pdf

Availability:

Product Overview


—— Product Description ——


Withair® Modular Air-Cooled Heat Pump Unit is a very intelligent heat pump system with flexible capacity output. It could adjust heating capacity output automatically according to requirements. It is much more energy-saving with a long lifespan.

 

Withair® Modular Air-Cooled Heat Pump Unit is a kind of central air conditioner which adopts air as the cooling & heating source and water as cooling & heating medium. With rich experience in R&D, design and application, Withair® constantly lanuched new environment-friendly modular units, which improves the structures, systems and programs based on original products, and designs special series of comfortable and technological units. The environment-friendly modular unit has complete functions and various specifications, with basic modules of any combination available for different models. Withair® offer quiet, reliable, energy efficient equipment. These units incorporate high quality compressors, state-of-the-art coil design, and innovative packaging. As a sort of integrated equipment, it needs no cooling tower, cooling water pump, boiler and corresponding auxiliary parts, which makes the system more simple, saves installation space, convenient maintenance and energy saving, thus it is very suitable for areas that are short of water. several modules can be formed in to a air-cooled heat pump module unit by connecting each module's inlet & outlet pipeline in parallel. with a system without cooling water, with simple pipelines, moderate cost, short construction period, allowing staged investment, the whole unit consists of 1~16 modules and the maximum capacity is 9,040kW.


Withair® Modular Air-Cooled Heat Pump Unit can be widely applied to civilian projects and industrial projects, such as hotel, villa, restaurant, hospital, factory, etc. it is a wise choice for areas where water is insufficient or there are strict limits on  noise level and surroundings. Each unit is verified for total unit performance before shipping to insure quality standards are inherent in every unit.


Unit adopts modular design, relatively independent modules units can be any combination and through microcomputer for centralized control, unit according to the change of load start-stop corresponding number of module unit to adjust the supply of cold (heat) capacity, to achieve the goal of high efficiency and energy saving. Units can effectively under the climatic conditions of heating at -20℃ and heat unit during normal operation the system is 3 times more than ordinary electric heater, winter climate is relatively low and no boiler or other heating conditions particularly applicable areas. with FCU, VAV and AHU and fresh air units, semi-central air conditioning system has the flexible layout, beautiful shape, saving space, convenient adjustment, low running noise, etc.


R410A CLASSICAL MODULAR UNIT


The new generation environment-friendly modular air-cooled unit is based on years of experience in R&D and design, which is greatly improved in aspects of the structure, system and microcomputer control technology, providing wider operation range of refrigeration and heating, and higher adaptability to applications with requirements on comfort and technology. There are basic modules of any combination available for different models, and at most 16 modules can be connected in parallel.


—— Excellent Capacity ——

Units of the same model or different models can be combined freely. Each group can combine up to 16 modules.


—— Intelligent Defrosting Technology, Non-stop When Defrosting ——

The unit control system can determine whether defrosting is necessary according to the ambient temperature in heating mode, evaporating temperature and running time; when defrosting conditions are met, the unit will automatically activate the defrosting program to complete defrosting within a short time and provide heating operation efficiency up to over 90% , ensuring the optimum heating capacity and high COP.


—— Free Master Module Design ——

Any single unit can operate as the master once connected with the wired controller. It overcomes the problem that the whole system would fail to work properly when the fixed master unit malfunctions.


—— Intelligent Air Volume Management ——

The shared duct system is adopted to greatly expand the operating range. The single-module unit can automatically increase or reduce fans based on the ambient temperature to achieve optimal matching between air volume and load and deliver outstanding performance.


—— Intelligent Energy Management Technology ——

The Unique intelligent energy regulation technology in multi-module combination ensures that each module loads or unloads a refrigerant circuit before loading or unloading other refrigerant circuits in the single module, thereby providing higher efficiency, stability and IPLV.


—— Widely Operation Range ——

        Low temperature cooling: 5°C ~ 48°C

        High temperature heating: -15°C ~ 48°C


—— Compact Design And Smaller Footprint ——

Unique and compact structure results in small size and occupied area, significant reductions in installation space and cost; the unit is compact and easy to install. A 136kW unit covers floor space of only 2.4m2, a 50% reduction compared to its equivalents.


—— Reliable Hermetic Scroll Compressor ——

Unit adopt reliable hermetic scroll compressor, which is high efficient, energy saving and operates stably, with low noise, slight vibration and long service life.


—— V-Shaped Condenser ——

The V-shaped condenser has used condenser has used an integral reinforcing metal frame, internal thread and tripe anti-frosting features (patented design of open-window hydrophilic aluminum foil + bottom elevated + one-way valve), providing higher structural stability and corrosion resistance; with heat exchange efficiency improved through full use of heat exchange area, low tendency to dust accumulation and frosting in winter, low loss of pressure, smoother drainage and higher reliability.


—— Efficient Shell And Tube Heat Exchanger ——

The waterside efficient shell and internal thread heat exchanger is of helical baffle type, with better heat transfer performance and higher resistance to freezing than plate heat exchanger, lower water resistance and lower requirements for water quality.


—— Saw-shaped Condenser Fan Blades ——

Compared to plastic impellers, the saw-shaped condenser fan blade provide large air volume, high durability and high air supply efficiency with low noise.


—— High Precision Electronic Expansion Valve ——

The electronic expansion valve achieves 480 regulating range, supplemented by Withair's patented precision throttle control technology to realize dynamic matching in refrigerating system, fully improve the optimum efficiency of each component and ensure the optimum condition of system operation pressure and temperature.


—— New R410A Environment-friendly Refrigerant ——

R410A environment-friendly refrigerant does not contain chlorine which destroys the ozone layer, and the ozone layer destruction system (ODP) is zero. At the same time, it effectively reduces CO2 emission, has stronger anti-low temperature ability and higher cooling efficiency.


—— In House Engineered Microprocessor Control ——

The Withair control panel is fully upgraded based on origin control panels with years of experience in R&D and design, which combines more functions including phase sequence detection, current detection, RS-485 communication interface, delivering stronger performance, utility, standardization, convenience and universality. The USB interface is so provided to facilitate later-stage maintenance and upgrade of control function. The panel is supplemented by Withair developed control program which offers full operation control and multiple safety protection functions.


—— Multiple Protection Functions, Providing Safety And Reliable ——

The unit has multiple safety protection functions which ensure safety and stable operation of the unit and systems. 

The water flow switch and multiple anti-freezing program designs protect the unit and systems in an all-round way.


—— Super Protection Function To Ensure The Safety Of System Operation ——

The unit is equipped with a fully functional protection module, with the industry‘s most complete 13 kinds of safety protection

functions and powerful fault diagnosis function as follows:

Power phase loss, reverse phase protection;

Current overload protection;

Insufficient water flow protection;

Frost protection;

Pump overload protection;

Water pump linkage protection;

Fan motor overload protection;

Compressor exhaust pressure is too high protection;

Compressor return air pressure is too low protection;

Compressor exhaust temperature is too high protection;

Compressor intelligent scroll temperature protection;

Cooling operation cooling water temperature is too low protection;

Overheating protection of cooling water temperature in heating operation;


—— New Touch-wire Controller, Easy To Control The System ——

A set of wire controller can meet up to 16 modules parallel at the same time to achieve centralized control, and users can know the operation and fault state of the unit through the wire controller in time.


Withair® New Touch-wire Controller, Easy To Control The System


—— Ultra-low Temperature And Wide Temperature Working Conditions Operation ——

    

The reliable operating range of  Withair series module unit is -26℃~48℃, when ambient temperature at -26℃,

unit still can be strong heating, which can realize the stable operation under the wide temperature range of -26℃~48℃.

Withair-heat-pump-chiller



R410A TOTAL HEAT RECOVERY MODULAR UNIT


Withair's total heat recovery modular air-cooled chiller & heat pump unit uses the environment-friendly refrigerant R410A and combines the features of Withair's air-cooled chiller & heat pump unit and air-source heat pump water heater unit. It has five modes: A/C cooling, A/C heating, heat recovery, heat pump water heating, A/C heating + heat pump water heating, widely applied in places requiring central air conditioning and water heating, such as: hotels, schools, restaurants, hospitals, villas, bath centers and industry use.


—— Free Domestic Hot Water ——

In the A/C cooling mode, the unit can recover waste heat and provide free domestic hot water to 55℃. The unit replaces the boiler to meet the user needs for hot water, saves initial investment, eliminates the need for machine room, and saves the building area and energy for environmental protection.


—— Less Occupied Area ——

A single module covers a floor area of only 1.86m2 which is the smallest in the industry, leaving larger valuable space for customers. The unit can substitute the boiler, eliminates the need for machine room, and saves initial investment and building area.


—— Compact Design And Complete Functions ——

In the A/C cooling mode, the unit can recover waste heat and provide free domestic hot water to 55℃. The unit replaces the boiler to meet the user needs for hot water, saves initial investment, eliminates the need for machine room, and saves the building area and energy for environmental protection.


—— Efficient Components Providing Higher Efficiency —— 

The unit employs efficient shell and tube heat exchanger, fan, and heat recovery unit, with optimized pipeline design, providing comprehensive energy efficiency up to 8.24 under conditions of cooling + heat recovery.


TOTAL HEAT RECOVERY OPERATION MODE


There are five operation modes including cooling, heat recovery, A/C heating, heat pump water heating, heating + heat pump water heating, which satisfy the user needs for air conditioning throughout the year and provide domestic hot water.



—— Cooling Mode ——

In summer or transition season needing cooling but not hot water, this mode can be used. In such case, the unit operates for cooling only, just like a standard air-cooled heat pump unit.


—— Heating Mode ——

In circumstances where only domestic hot water is needed instead of cooling or heating, this mode can be used. In such case, the unit only provides domestic hot water, just a standard air source heat pump water heater unit.


—— Heat Recovery Mode ——

In circumstances where both cooling and production of domestic hot water are needed, this mode can be used. In such case, the unit automatically selects the optimal operation mode based on the needs for air conditioning and water heating to produce chilled water for air conditioning and domestic hot water for everyday use.


—— Heat Pump Water Heating Mode ——

In circumstances where only domestic hot water is needed instead of cooling or heating, this mode can be used. In such case, the unit only provides domestic hot water, just like a standard air source heat pump water heater unit.


—— Heating + Heat Pump Water Heating Mode ——

In winter or other circumstances where both heating and domestic hot water are needed, this mode can be used. In such case, the water heating mode is preferred by default to ensure use of domestic hot water; then at the “idle time” when the demand for hot water is satisfied, the unit automatically switches to the heating mode to meet the needs for heating. Users may set the heating mode as the priority as required to ensure heating effect.



R410A YEAR-ROUND COOLING MODULAR UNIT


Withair's new generation of year-round cooling modular unit is applicable for industrial applications, and requirements on energy saving and environment protection. It can operate for refrigerant at the ambient temperature of -10℃~48℃ all the year round, with environment friendly refrigerant R410A, advanced electronic expansion valve control technology, efficient shell and tube heat exchanger, EC fan with steplless speed regulation, fully meeting the requirements of various industry applications for chilled water throughout the year.


—— Widely Operation Range of Cooling ——


The modular water chiller unit is specially designed and can run in all weathers at the ambient temperature of -10℃~48℃.


—— EC Fan With Stepless Speed Regulation ——


The condensate fan employs the EC motor of which the speed is variable between 20%~100% to ensure that condensing pressure is within the range of safe operation under all conditions for longer service life.



—— The Key Advantages Include ——


● ECO friendly refrigerant R410a, R407c.

● Flexible configurations with top or side piping and  front or side control box.

● Large panels for accessibility to compressor and controls sections

● Plate type, coaxial tube-in-tube heat exchanger for high performance, reliability, and resistance to freezing.

● Multi-function: provide cooling only, cooling with hot water, heating only and heating with hot water, hot water, total heat recovery, partial heat recovery for domestic hot water heating (55℃).

● Unit choose efficient rotary or scroll compressor, the use of high efficient heat exchanger technology processing, condensation temperature greatly reduced.

● When multiple units were combined into a system, because each unit can be individually ON/OFF; wide range of system energy regulation and running costs fell by more 40%.

● Unique compressor anti-vibration technology (patent ZL 2020 2 0246589.1) and sound attenuation material ensure ultra-quiet performance.

● Advanced microcomputer automatic control system, with protection of high and low pressure, overload, low voltage, phase lack, and low temperature etc., with terminal for the external pumps, and displays and alarms malfunction.

● Running ambient range from -20℃ to 50℃.

● Built-in hydraulic module for option.

● Multi-system design and wear-and-tear management technology reduces electric impulse and extend service life.

● Modular network function: unit control system is equipped with the network communication, the user can control operating units quantity according to the actual use load, make user side water system utilities, to realize the automatic device management automation and energy management.

● Smart microchip control and large LCD user interface, capable of one-key startup.

● Automatic intelligent reset. Unit shall automatically restart 5 minutes after shutdown if the fault has cleared. Should a fault occur 3 times sequentially, then lockout will occur.

● Humanized design, widened application scope: the unit’s temperature settings for room, hot water, water intake/outlet, freeze protection, and compressor exhaust can be adjusted on-site according to environmental conditions.

● Communication adapter connection the unit to BMS(Building Management System) is an optional accessory, please get in touch with us or our distributor if required.

● Unit with multi-protection to guarantee the unit running stability and security, such as: high/low voltage, low oil level protection, exhaust temperature, antifreeze, power lack/reverse phase, water system cut off. operating condition with small change range stable operation, safe, reliable and long service life.

● Easy installation,  simple water piping system configuration, you can make design partition and divide second installation.

● Quality components selection

   Compressors and refrigeration accessories (such as dry filter, thermal expansion valve, liquid supply solenoid, liquid level mirror, high/low pressure control devices) all chosen world-renowned brand products to ensure that the unit reached an excellent level of performance. Using the most advanced DAE / DAC efficient heat transfer pipe, heat transfer surface with internal ribbed tube makes the heat transfer coefficient substantially increased; the heat exchanger unique structural design, the best way of copper tube layout and precision of refrigerant control technology, greatly improved the efficiency of heat transfer.

● Perfect control

     1) Computerized control with standby manual operation system

     2) Compressor Operation timing

     3) Compressor automatic start-up sequence,

     4) Alarm signals

     5) Alarm reset

     6) Water temperature control

     7) Manual reset high pressure switch, Automatic reset low pressure switch

● Equipped self-diagnosis function, and automatically eliminate software problem

● Protections that ensure its safe and stable operation:

1) Reverse phase

2) Lack phase

3) High/low pressure

4) Gas discharge

5) Outlet water temperature too low (high)

6) Water stopped

7) Antifreeze

8) Compressor overheat etc.

● All the components covered with casing, keeps damages to cooling and electrical system away.

● Small size, light weight, easy for installation, transfer and maintenance, can be put into use just make water pipes and the power supply cable be connected at the site.

● EVI compressor as option. EVI compressor-enhanced vapor injection, Vapor-injected method can effectively improve heat capacity, prevent higher discharge temperature of compressor and guarantee operating stability of unit at low temperature). 

● STRUCTURE

      Panels and frame are made from galvanized steel protected with polyester powder painting to ensure total resistance  

      to atmospheric agents.

● HERMETIC SCROLL COMPRESSORS

      Single phase type and 3-phase scroll type compressors, with built-in thermal overload cut-out and crankcase heater, mounted on rubber vibration dampers.

● EVAPORATOR & CONDENSER

      High efficiency plate type heat exchanger, tube in tube heat exchanger, shell and tube heat exchanger, factory-insulated with flexible close cell material.

● REFRIGERANT CIRCUIT

      Copper tube connection with charge valves, filter, thermostatic expansion valve, gas-liquid separator, high pressure switch and low pressure switch. The heat pump units are complete also with 4-way valve and one way valve.

● HYDRAULIC CIRCUIT

      No build in water circuit as standard.

● ELECTRIC PANEL

      Consists of: Compressor contactor, Compressor protection breaker, Microprocessor with function display.

● OPTIONAL PARTS

Source side water flow switch, source side water pump, & user side water flow switch, user side water pump,  hot water pump

Expansion tank

Metallic filter for the water circuit

Build in water circuit

Modular type

Heat recovery for domestic hot water (55℃)


—— You May Like ——


 Withair® Modular Air Cooled Heat Pump & Water Chiller     Concealed Type Fan Coil Unit   Withair® Variable Air Volume Unit     Withair® Air Handling Unit_1Withair® Air Handling Unit_1       Withair® Insulation materials_2         Termostat controls (2)

Air Cooled Heat Pump        +        Fan Coil Unit        +        Variable Air Volume Unit      +     Air Handling Unit     +    Insulation materials       +      Thermostat



Technical Specifications

                                                                                                                    

—— Specifications (ON/OFF Version , Standard Single Modular Unit) ——

Model No.

W01R1-72

W01R1-105

W01R1-140

W01R1-175

W01R1-210

W01R1-280

W01R1-363

W01R1-565

Nominal cooling capacity

kW

72

105

140

175

210

280

363

565

US.RT

20

30

40

50

60

80

100

160

EER

3.35 

3.36 

3.33 

3.35 

3.36

3.38 

3.38 

3.35 

Nominal heating capacity

kW

76

112

147

185

222

295

382

592

US.RT

21.6

31.8

43.2

54.3

64.8

87.0

108.5

174.0

COP

3.69

3.61

3.58

3.67

3.66

3.66

3.65

3.65

Power supply


380V/3P/50Hz (400V/415V/3P/50Hz, 230V/380V/460V/3P/60Hz   as option)

Compressor

Type


Advanced fully hermetic scroll compressor

Brand name


Daikin, Copeland, Hitachi, Panasonic, Mitsubishi as option

Quantity


2

2

2

4

4

4

8

8

Input   power

kW

19.2

27.0

36.0

46.7

56.1

74.5

96.9

150.6

Safe protection device

High/low pressure switch, overload protection, counter clock wise and   short phase protection

(power   phases sequence protection),lack water(water-flow switch),anti-freezing   protection, etc.

Air side heat exchanger

(Condenser)

Type


High efficiency exchanger copper tube and aluminum fin coil

Air flow volume

m³/h 

24000

      36000

      45000

      76000

     112000

      142000

     168000

     284000

Fan motor type


Low noise, high efficiency, waterproof and weatherproof axial flow   type 

Fan motor power

kW

1.4 

2.0 

2.8 

4.5 

6.0

9.2 

11.7 

17.1 

Water side heat exchanger

(Evaporator)

Type


High efficiency shell-and-tube heat exchanger

Water flow rate

m³/h

11.7

16.5

21.4

29.3

35.6

44.8

58.5

90.2

Water pressure drop

kPa

40 ~ 80

Max. working pressure

MPa

1

Dimension

Length*width*height

mm

2065*1030*1974

2316*1306*2360

4360*2290*2020

4710*2290*2020

5650*2260*2590

9420*2290*2590

Noise level

dB(A)

65

68

71

73

74

76

78

83

Water proof level


IPX4

Electric shock protection


I

Refrigerant

Type


HFC- R410A

Charging rate

kg

16

25

30

43

55

62

84

128

Net weight

kg

840

1350

1880

2720

3150

3860

4290

7850

Entering/leaving water pipe

Inch 

2-1/2

2-1/2“

2-1/2“

3“

3

3“

3“

3“

Optional auxiliary electric heater

kW

15

25

30

50

60

60

80

100

Control type


Wired control, manual or automatic start up, the running status   display and malfunction alarm, etc.

Notes: 

1. Nominal cooling operating conditions: entering chilled water temperature 12℃, leaving temperature 7℃; outdoor dry bulb temperature 35℃,wet bulb temperature 24℃.

    Nominal heating operating conditions: entering hot water temperature 40℃,leaving temperature 45℃; outdoor dry bulb temperature 7℃,wet bulb temperature 6℃;

2. The controllers need to ordered separately, including wire controller, communication line, IOM, temperature sensor and water flow switch.

3. These parameter were tested according to pure water, not include anti-freezing liquid and water pump power.

4. Chiller unit without heating parameters.

5. In actual use, the cooling/heating loss should be considered after the installation of the system piping, pumps, valve, dirt, etc. about 6%.

6. For other working conditions or capacity parameters, please contact Withair for cooling ambient condition under 5℃.
7. There will be no further notice if the parameters changes due to product optimization.
8. The units of the same model or different models can be combined freely. Each system can combine up to 16 modules.
9. Manufacturer reserves the right to make changes to above specifications without prior notice, please refer to the factory configuration when purchasing.


Conditions

Water   side

Air side

Nominal   working condition

Working range

Nominal   working condition

Working range

EWT   (℃)

LWT (℃)

EWT   (℃)

LWT (℃)

Dry bulb temperature (℃)

Dry bulb temperature of outdoor (℃)

Cooling

12

7

5 ~ 15

2.5 ~ 8

35

12 ~ 50

Heating

40

45

30 ~ 50

2.5 ~8

7

- 26 ~28

Note: LWT - leaving water temperature, EWT - entering water   temperature


—— Various Models Combines Capacity Parameter Table ——

Model & modular quantity

W01R1-72

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Cooling capacity

kW

72

144

216

288

360

432

504

576

648

720

792

864

936

1008

1080

1152

Heating capacity

kW

76

152

228

304

380

456

532

608

684

760

836

912

988

1064

1140

1216

Water flow rate

m3/h

11.7

23.4

35.1

46.8

58.5

70.2

81.9

93.6

105.3

117

128.7

140.4

152.1

163.8

175.5

187.2

Model & modular quantity

W01R1-105

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Cooling capacity

kW

105

210

315

420

525

630

735

840

945

1050

1155

1260

1365

1470

1575

1680

Heating capacity

kW

112

224

336

448

560

672

784

896

1008

1120

1232

1344

1456

1568

1680

1792

Water flow rate

m3/h

16.5

33

49.5

66

82.5

99

115.5

132

148.5

165

181.5

198

214.5

231

247.5

264

Model & modular quantity

W01R1-140

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Cooling capacity

kW

140

280

420

560

700

840

980

1120

1260

1400

1540

1680

1820

1960

2100

2240

Heating capacity

kW

147

294

441

588

735

882

1029

1176

1323

1470

1617

1764

1911

2058

2205

2352

Water flow rate

m3/h

21.4

42.8

64.2

85.6

107

128.4

149.8

171.2

192.6

214

235.4

256.8

278.2

299.6

321

342.4

Model & modular quantity

W01R1-175

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Cooling capacity

kW

175

350

525

700

875

1050

1225

1400

1575

1750

1925

2100

2275

2450

2625

2800

Heating capacity

kW

185

370

555

740

925

1110

1295

1480

1665

1850

2035

2220

2405

2590

2775

2960

Water flow rate

m3/h

29.3

58.6

87.9

117.2

146.5

175.8

205.1

234.4

263.7

293

322.3

351.6

380.9

410.2

439.5

468.8

Model & modular quantity

W01R1-210

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Cooling capacity

kW

210

420

630

840

1050

1260

1470

1680

1890

2100

2310

2520

2730

2940

3150

3360

Heating capacity

kW

222

444

666

888

1110

1332

1554

1776

1998

2220

2442

2664

2886

3108

3330

3552

Water flow rate

m3/h

35.6

71.2

106.8

142.4

178

213.6

249.2

284.8

320.4

356

391.6

427.2

462.8

498.4

534

569.6

Model & modular quantity

W01R1-280

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Cooling capacity

kW

280

560

840

1120

1400

1680

1960

2240

2520

2800

3080

3360

3640

3920

4200

4480

Heating capacity

kW

295

590

885

1180

1475

1770

2065

2360

2655

2950

3245

3540

3835

4130

4425

4720

Water flow rate

m3/h

44.8

89.6

134.4

179.2

224

268.8

313.6

358.4

403.2

448

492.8

537.6

582.4

627.2

672

716.8

Model & modular quantity

W01R1-363

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Cooling capacity

kW

363

726

1089

1452

1815

2178

2541

2904

3267

3630

3993

4356

4719

5082

5445

5808

Heating capacity

kW

382

764

1146

1528

1910

2292

2674

3056

3438

3820

4202

4584

4966

5348

5730

6112

Water flow rate

m3/h

58.5

117

175.5

234

292.5

351

409.5

468

526.5

585

643.5

702

760.5

819

877.5

936

Model & modular quantity

W01R1-565

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Cooling capacity

kW

565

1130

1695

2260

2825

3390

3955

4520

5085

5650

6215

6780

7345

7910

8475

9040

Heating capacity

kW

592

1184

1776

2368

2960

3552

4144

4736

5328

5920

6512

7104

7696

8288

8880

9472

Water flow rate

m3/h

90.2

180.4

270.6

360.8

451

541.2

631.4

721.6

811.8

902

992.2

1082.4

1172.6

1262.8

1353

1443.2


—— Performance Parameter Correction Coefficient Table in Different Conditions ——

Cooling capacity

LWT ()

Ambient temperature ()

20

25

30

35

40

45

Cooling capacity

Input power

Cooling capacity

Input power

Cooling capacity

Input power

Cooling capacity

Input power

Cooling capacity

Input power

Cooling capacity

Input power

5

1.07

0.74

1.02

0.81

0.98

0.89

0.94

0.99

0.90

1.06

0.85

1.19

7

1.14

0.76

1.08

0.82

1.04

0.90

1.00

1.00

0.96

1.09

0.92

1.20

9

1.20

0.78

1.15

0.84

1.11

0.92

1.07

1.02

1.03

1.10

0.98

1.23

12

1.29

0.80

1.26

0.86

1.21

0.94

1.16

1.03

1.12

1.12

1.08

1.25

15

1.39

0.82

1.35

0.88

1.30

0.95

1.26

1.05

1.22

1.16

1.18

1.27

Note: LWT - leaving water   temperature, EWT - entering water temperature

Heating capacity

LWT ()

Ambient temperature ()

15

10

7

0

-5

-10

Heating capacity

Input power

Heating capacity

Input power

Heating capacity

Input power

Heating capacity

Input power

Heating capacity

Input power

Heating capacity

Input power

35

1.22

0.95

1.16

0.92

1.07

0.90

0.86

0.82

0.73

0.75

0.65

0.70

40

1.19

1.00

1.13

0.95

1.03

0.92

0.85

0.86

0.72

0.80

0.63

0.73

45

1.16

1.08

1.08

1.04

1.00

1.00

0.81

0.91

0.70

0.82

0.61

0.75

50

1.14

1.12

1.05

1.08

0.98

1.04

0.79

0.94

0.69

0.84

0.58

0.77

Note: LWT - leaving water   temperature, EWT - entering water temperature

Note: Above correction factors adapt to W01R1-72, W01R1-105, W01R1-140, W01R1-175, W01R1-210, W01R1-280, W01R1-363, W01R1-565

Projects Solutions

● Solution for Hotel : Heat Recovery Air-cooled Heat Pump + FCU + Floor Heating + Fresh Air Unit + Heat Pump Water Heater


Withair® Solution for Hotel Heat Recovery Air-cooled Heat Pump + FCU + Floor Heating + Fresh Air Unit + Heat Pump Water Heater

System Introduction:

In addition to reliably guaranteeing the use of air conditioners, this system can also guarantee 24/7 hot water supply; in the cooling season, users can get free hot water while using air conditioners for cooling; the cooling water system is omitted, and low the initial investment. ; Dual-purpose cooling and heating, no additional heating system is required; different air handling equipment can be configured according to the needs of different functions, such as fan coil units, variable air volume units, fresh air units, air handling units, etc.; modular configuration of the unit, it can realize non-stop maintenance; intelligent control, realizing quasi-linear energy adjustment with load changes, the system does not need a dedicated machine room, so it can release the effective space of the building and realize its economic value.


● Solution for Office Building: Air-cooled Heat Pump + Fan Coil Unit + Fresh Air Unit

Withair® Solution for Office Building Air-cooled Heat Pump + Fan Coil Unit + Fresh Air Unit

System Introduction:

In addition to the reliable protection of the air conditioner, the system eliminates the need for a cooling water system and has a small initial investment; it is dual-purpose for cooling and heating, without the need for additional heating systems; it can be equipped with different air handling equipment, such as fan disks, according to the needs of different functions Tubes, variable air volume units, fresh air units, combined air handlers; the modular configuration of the main engine can realize non-stop maintenance; intelligent control realizes quasi-linear energy adjustment with load changes, so that the system always maintains the highest operating efficiency. The annual operating costs are low. The system does not require a dedicated computer room, so it can release the effective space of the building and realize its economic value.


● Solution for Shopping Mall :  Air-cooled Heat Pump + Air handling Unit + Fresh Air Unit + Variable Air Volume Unit

Withair® Solution for Shopping Mall Air-cooled Heat Pump + Air handling Unit + Fresh Air Unit + Variable Air Volume Unit

System Introduction:

According to the characteristics of large flow of people and high demand for air volume in commercial places, the system adopts variable air volume units with large air volume and air handling unit and modular units configuration, which can realize non-stop maintenance; eliminates the need for cooling water system, and has a small initial investment; dual use of cooling and heating , No need to configure the heating system separately; in addition to ensuring the reliable operation of the system, intelligent control realizes quasi-linear energy adjustment with load changes. It can be easily switched to the mode of fresh air during the transition season, so that the system always maintains the highest operating efficiency. The annual operating costs are low. The system does not require a dedicated computer room, so it can release the effective space of the building and realize its economic value.


● Solution for Amusement Building :  Air-cooled Heat Pump + FCU + AHU + Fresh Air Unit + Heat Pump Water Heater


Withair® Solution for Amusement Building Air-cooled Heat Pump + FCU + AHU + Fresh Air Unit + Heat Pump Water Heater

System Introduction:

In addition to reliably ensuring the use of air conditioners, the system can also guarantee 24 hours of hot water supply for 365 days; the cooling water system is omitted, and the initial investment is small; the heating and cooling systems are dual-purpose, without the need for additional heating systems; the modular units configuration can be realized. The system capacity can also be increased at any time according to the operating conditions if the maintenance is disabled; intelligent control realizes quasi-linear energy adjustment with load changes. The system does not require a dedicated computer room, so it can release the effective space of the building and realize its economic value.



Packaging & Transportation

-

● 100% test before deliverying products.

● Products catalogue, installation & operation manual will be sent together.

● Tracking number will be sent to customer as soon as we ship the products.

● Item shipped in 25 working days against payment depends on the quantity.

● Four steps of pakacges, plastic film, foam, carton and plywood for stable transporation.

● Ocean shipping, railway shipment and air transportation are acceptable according to customer demand.


Withair® provides two styles package for different transporation modes:

(1). Standard package(free of charge): unit is wrapped with plastic film, which is suitable for container shipment & a few transshipment cargo;

  withair heat pump package_3withair heat pump shipment
(2). Special package(extra charge): unit is wrapped with plastic film and wooded box, which is suitable for bulk cargo transporation;
withair heat pump package_1

Previous: 
Next: 
Get Best Quote

Quick Links

Product Category

Get In Touch

   Withair Group (China) Limited
   Withair (Nanjing) Industries Co., Ltd
    Office number: + 86 25 86696286
    Mobile number: + 86 13915928183 (WhatsApp)
    E-mail address: info@withair.cn ; jed@withair.cn
    Factory A: No.6 Lukou Chuangzhi Industrial Park, Nanjing,China,211113
    Factory B: No.9 Dongshan Bridge Industrial Park, Nanjing,China,211153
Home